2XSY 12/20 KV - IEC
2XSY 12/20 KV - IEC
Single core MV cable XLPE insulated with PVC outer sheath. Rated voltage 12/20 KV
Read moreCU/XLP/PVC 20 1X 50/16
Nexans ref. 13000100
- Packaging: Cut to length (m)
- Conductor cross-section: 50 mm²
- Phase Conductor Cross Section: 50 mm²
- Screen section: 16 mm²
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 26.0 mm
CU/XLP/PVC 20 1X 50/25
Nexans ref. 13005173
- Packaging: Cut to length (m)
- Conductor cross-section: 50 mm²
- Phase Conductor Cross Section: 50 mm²
- Screen section: 25 mm²
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 26.0 mm
CU/XLP/PVC 20 1X 70/16
Nexans ref. 13000101
- Packaging: Cut to length (m)
- Conductor cross-section: 70 mm²
- Phase Conductor Cross Section: 70 mm²
- Screen section: 16 mm²
- Nominal outer sheath thickness: 1.9 mm
- Nominal outer diameter: 28.0 mm
CU/XLP/PVC 20 1X 70/25
Nexans ref. 13005174
- Packaging: Cut to length (m)
- Conductor cross-section: 70 mm²
- Phase Conductor Cross Section: 70 mm²
- Screen section: 25 mm²
- Nominal outer sheath thickness: 1.9 mm
- Nominal outer diameter: 28.0 mm
CU/XLP/PVC 20 1X 95/16
Nexans ref. 13000102
- Packaging: Cut to length (m)
- Conductor cross-section: 95 mm²
- Phase Conductor Cross Section: 95 mm²
- Screen section: 16 mm²
- Nominal outer sheath thickness: 1.9 mm
- Nominal outer diameter: 30.0 mm
Description
Description
Standards
-
ProductIEC 60502-2
-
TestIEC 60332-1-2
Application
Single core MV cable suitable for outdoor and indoor installation, in air, in grounds, and in cable ducts.
According to CPR regulation the cable is Euroclass Eca
Construction
The cable is consisted of stranded copper conductor, conductor screen of semiconducting compound, XLPE insulation, insulation screen of semiconducting compound, copper wires metallic screen, PVC outer sheath.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Copper
Conductor flexibility
Stranded class 2
Conductor shape
Circular
Material of the inner semi-conductor
Semi-conducting compound
Insulation
XLPE
Material of the external semi-conductor
Semi-conducting compound
Screen
Copper wire
Outer sheath
PVC
Dimensional characteristics
Dimensional characteristics
Number of cores
1
Nominal insulation thickness
5.5 mm
Electrical characteristics
Electrical characteristics
Rated Voltage Uo/U (Um)
12 / 20 (24) kV